PSR-78-8527-PKG
- Tested and approved under UL 62368-01 by Underwriters Laboratories
- NFPA 72, NFPA 1221, IFC code compliant
- Include PSR-ANN-L annunciator to provide visual and audible alarms with the option to extend up to 1000 ft
- Supports 700/800 MHz, including Band 14 analog and digital systems
- Alarming output to supervised circuits for: antenna, amplifier, AC or DC power supply, battery, annunciator disconnect, and charger failure including oscillation detection with automatic amplifier shutdown routine
- IP66 enclosure for both indoor and outdoor environments
- Supports FCC Part 90 Class B wideband repeater designations
- Up to 85 dB of gain and up to 27 dBm composite output power
- Supports P25 Phase 1 (FDMA) and Phase 2 (TDMA) communications
PSR-78-9533
- NFPA 72 2016 code compliant and FirstNet compliant
- Alarming output to supervised circuits for: antenna, amplifier, AC or DC power supply, battery, and charger failure including oscillation detection with automatic amplifier shutdown routine
- IP66 compliant enclosure for both indoor and outdoor environments
- Simultaneously supports FCC Part 90 Class A narrowband and Class B wideband repeater designations
- Up to 95 dB of gain and up to 33 dBm downlink and 30 dBm uplink output power per band
PSR-78-9537
- NFPA 1221 2016 code compliant and FirstNet compliant
- Alarming output to supervised circuits for: antenna, amplifier, power supply, battery, and charger failure
- IP66 compliant enclosure for both indoor and outdoor environments
- Simultaneously supports FCC Part 90 Class A narrowband and Class B wideband repeater designations
- Up to 95dB of gain and up to 37 dBm downlink output power per band and up to 30 dBm uplink output power shared
- Software defined filtering of up to 32 non-contiguous narrowband support
PSR-VU-9537
- NEMA 4X compliant enclosure suitable for both indoor and outdoor environments
- High performance bandpass filter
- Alarming output to supervised circuits for antenna failure, amplifier failure, AC failure, power supply, battery, and charger failure
- Supports up to 1 wideband and up to 8 non-contiguous narrow bands
- Center frequencies adjustable in 0.5 KHZ step
- Bandwidths adjustable in 250 KHz step
- AC Power for 110 VAC / 220 VAC
ADRF-BBL-X
- UL 2524 certified with PSR-78-9533-X, PSR-78-9537-X, and PSR-VU-9537-X
- Includes single cable between battery and DAS / repeater
- NFPA 2016 compliant including 12-hour runtime and battery disconnect alarm
- Increase runtime by adding unit using parallel cable (ADRF-BBX-CBL-21P)
- Increase voltage by adding unit using series cable (ADRF-BBX-CBL-21S)
- Available in 12V, 24V, 48V solutions
- Optional wall mount kit available (ADRF-BBL-X-WMK)
ADRF-BBS-X
- Includes single cable between battery and DAS / repeater
- NFPA 2016 compliant including 12-hour runtime and battery disconnect alarm
- Increase runtime by adding unit using parallel cable (ADRF-BBX-CBL-21P)
- Increase voltage by adding unit using series cable (ADRF-BBX-CBL-21S)
- Available in 12V, 24V, 48V solutions
- Optional wall mount kit available (ADRF-BBS-X-WMK)
ADRF-BBx-N4
- Supports all ADRF DAS and repeaters
- NFPA 2016 compliant including 12 hour runtime, battery disconnect alarm, and IP66 guaranteed rated enclosure
- Enables increased runtime by adding unit
- Available in 12V, 24V, 48V
- Includes single cable between battery and DAS / repeater
Contact Us