Product features include :
- Wide range of Automatic Voltage Regulation (AVR)
- Temperature compensated charging
- Fast transfer time < 5ms typical
- SNMP network card, RS-232 and USB ports included
- LCD screen for quick access to system diagnostics
- Front panel connections for easy install
- Forced air cooled with fan filter (field replaceable)
- Alarm contacts (six sets)
- 19” rack or cabinet mounting
- AC Wiring: hard wired AC input/output
Engineered to meet the demanding applications and harsh environments of outdoor cabinets, traffic and Intelligent Transportation Systems (ITS), public safety and remote communication sites;
the Rugged AC UPS features a wide AC input voltage range of 88 – 152V AC
and operates at extreme hot and cold temperatures.
Product Specifications
Input Voltage Range: | 88 – 152V AC, User Programmable. Default set @ 100 – 130V AC |
Transfer time (typical): | UPS Mode: 5ms |
Normal Mode: | 20ms |
Generator Mode: | 25ms |
Site Fault Detection: | Yes |
Efficiency (Line Mode): | 95% typical |
Output Waveform: | Pure sine wave |
Nominal Output Voltage: | 120V AC, +/- 5% |
Output Frequency: | 50/60 Hz +/- 0.1% |
Nominal DC Voltage: | 48V DC (2000V A and 1200V A) 24V DC (700V A) |
Low DC Voltage Warning: | 48V DC: 42 – 55V DC (adjustable) 24V DC: 21 – 27.5V DC (adjustable) |
No Load Power Consumption: | 28 watts at rated nominal DC Voltage |
Output Short Circuit Protection: | Output breaker/electronic current limit/firmware |
Surge Capacity: | 200% (rated power for 5 secs) |
Back Feed Protection: | Yes |
Charging Current: | 2A/4A/6A/8A/10A adjustable |
Charging Algorithm: | 3 step |
Operating Temperature: | -40° to 80° C |
Storage Temperature: | -50° to 80° C |
Relative Humidity: | 5 to 95% non-condensing |
Audible Noise: | <53dB |
Cooling: | Forced air, field replaceable fan and filtered |
EMI: | Class A FCC/CISPR [EN50091-2: 1995] |
Surge Protection: | IEEE/ANSI C.62.41 & 2KV, L-N |
Certifications: | TUV Rhineland certified to UL Standard 1779, CSA Standard 107.3 & FCC Part15A (EMC) specifications |
Overload Protection: | 5s @ ≥ 125 – 150% load, 60s @ 110 – 125% load THD (Bat. Mode) <3% (full resistive load) |
Load Crest Factor: | 3:1 @ rated load |
Contact Us
Error: Contact form not found.