Product features include :

  • NEMA 4 enclosure, powder coated steel
  • Front panel “test” alarm button
  • Ultra bright light emitting diodes
  • Microprocessor controlled
  • Wide operating voltage range: 12, 24 and 48 volt systems
  • Eight (8) Form-C alarm relays
  • Alarm silence button (24 Hrs.) located inside enclosure
  • Easily adapted to fit nearly any situation, 12, 24 and 48V DC battery back-ups
  • Selectable Alarm Input: can be activated by contact open (default) or contact closure upon alarm

Customization options

  • Master/Slave Multiple Annunciators: Allows 1 master and up to 15 remotes to be wired in sequence via RS-485 connectivity
  • Summary Alarm (Auto Dialer): A designated alarm relay can activate when any 1 of the 7 alarm inputs are activated in order to activate an auto-dialer
  • Loss of Annunciator Panel Power Alarm: Provides a normally closed alarm contact that opens upon loss of power to annunciator panel. Contact factory for more information

The first five alarms are wired for NFPA mandated alarms; AC Power Failure, Low Battery, Charger Failure, BDA Failure and Antenna Failure. Three alarm relays are available for site customization; additional alarms could include Donor Antenna Disconnection, Active, RF Emitting Device Malfunction, System Component Malfunction, and more. A normal AC power LED and lamp test button are included.

Product Specifications

Input: 60V DC
Input Current Draw: <100 mA
Max. Power: 4.5 watts
Operating Temperature: -4 to 122° F (-20 to 50° C)
Heat Dissipation:<12 watts (worst case) <12 watts (worst case)
Relay Switching Current:  2-Amp DC (resistive)
Enclosure: NEMA-4, UL listed, welded steel with IP-66 rating, quarter turn latch, bonding studs on door and enclosure, continuous stainless steel hinge with welded brackets for enclosure mounting, one each NPT-1/2 and NPT-3/4 liquid tight cord grips included.
Enclosure Size including Mounting Flanges (H x W x D): 11.375” x 8” x 4.75”
Weight: 7.35 lbs.